2014-05-05 15:49:41PLUMBING PLAN REVIEW
 PERMIT: 14050005
 ADD: 1741 PALM BEACH LAKES F05
 CONT: TBD
 TEL: (561) 401-1349
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MAY 05/2014
 ACTION: DENIED
  
 1) SHEET P1.0 THE FLOOR DRAINS INDICATE WITH RESEAL BUT
 DO NOT INDICATE THE RESEAL IS A TRAP PRIMER.
 2010 FBC-P 1002.2 DESIGN OF TRAPS.
 FIXTURE TRAPS SHALL BE SELF-SCOURING. FIXTURE TRAPS
 SHALL NOT HAVE INTERIOR PARTITIONS, EXCEPT WHERE SUCH
 TRAPS ARE INTEGRAL WITH THE FIXTURE OR WHERE SUCH TRAPS
 ARE CONSTRUCTED OF AN APPROVED MATERIAL THAT IS
 RESISTANT TO CORROSION AND DEGRADATION. SLIP JOINTS
 SHALL BE MADE WITH AN APPROVED ELASTOMERIC GASKET AND
 SHALL BE INSTALLED ONLY ON THE TRAP INLET, TRAP OUTLET
 AND WITHIN THE TRAP SEAL.
 2010 FBC-P 1002.3 PROHIBITED TRAPS.
 THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS
 THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEA.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676