| 2014-05-05 16:17:46 | FUEL GAS/ PLUMBING PLAN REVIEW |
| | PERMIT: 14050005 |
| | ADD: 1741 PALM BEACH LAKES F05 |
| | CONT: TBD |
| | TEL: (561) 401-1349 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY MAY 05/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE P3 SHEET INDICATES LP GAS TO THE FOOD COURT |
| | AREA, PLEASE SEE ONLY NATURAL GAS IS BEING SUPPLIED TO |
| | THE FOOD COURT. THE ONLY PLACE LP GAS IS ON SITE IS TO |
| | THE GENERATORS. PLEASE CORRECT PLANS AND TABLES FOR |
| | NATURAL GAS. 2010 FBC-FUEL GAS TABLE 402.4 (1-22), |
| | NATURAL GAS. |
| | |
| | 2) THIS SHEET UNDER THE HEADING OF NOTES INDICATES THE |
| | USE OF POLYEHTYLENE PIPE OF SCHEDULE 40 GALVANIZED |
| | METAL PIPE. THE PLAN ALSO INDICATES 12 FEET TO BE RUN |
| | IN THE WALL. PLEASE SEE 2010 FUEL GAS SECTION 404.3 |
| | PIPING IN CONCEALED LOCATIONS. PORTIONS OF A PIPING |
| | SYSTEM INSTALLED IN CONCEALED LOCATIONS SHALL NOT HAVE |
| | UNIONS, TUBING FITTINGS, RIGHT AND LEFT COUPLINGS, |
| | BUSHINGS, COMPRESSION COUPLINGS AND SWING JOINTS MADE |
| | BY COMBINATIONS OF FITTINGS. |
| | EXCEPTIONS: |
| | 1. TUBING JOINED BY BRAZING. |
| | 2. FITTINGS LISTED FOR USE IN CONCEALED LOCATIONS. |
| | |
| | 3) THE P3 NOTE 2 INDICATES SCHEDULE 40 METAL PIPE OR |
| | POLYEHTYLENE PLASTIC PIPE. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" ORITS EQUIVALENT |
| | BE USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 |
| | |