2014-05-05 16:17:46FUEL GAS/ PLUMBING PLAN REVIEW
 PERMIT: 14050005
 ADD: 1741 PALM BEACH LAKES F05
 CONT: TBD
 TEL: (561) 401-1349
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MAY 05/2014
 ACTION: DENIED
  
 1) THE P3 SHEET INDICATES LP GAS TO THE FOOD COURT
 AREA, PLEASE SEE ONLY NATURAL GAS IS BEING SUPPLIED TO
 THE FOOD COURT. THE ONLY PLACE LP GAS IS ON SITE IS TO
 THE GENERATORS. PLEASE CORRECT PLANS AND TABLES FOR
 NATURAL GAS. 2010 FBC-FUEL GAS TABLE 402.4 (1-22),
 NATURAL GAS.
  
 2) THIS SHEET UNDER THE HEADING OF NOTES INDICATES THE
 USE OF POLYEHTYLENE PIPE OF SCHEDULE 40 GALVANIZED
 METAL PIPE. THE PLAN ALSO INDICATES 12 FEET TO BE RUN
 IN THE WALL. PLEASE SEE 2010 FUEL GAS SECTION 404.3
 PIPING IN CONCEALED LOCATIONS. PORTIONS OF A PIPING
 SYSTEM INSTALLED IN CONCEALED LOCATIONS SHALL NOT HAVE
 UNIONS, TUBING FITTINGS, RIGHT AND LEFT COUPLINGS,
 BUSHINGS, COMPRESSION COUPLINGS AND SWING JOINTS MADE
 BY COMBINATIONS OF FITTINGS.
 EXCEPTIONS:
 1. TUBING JOINED BY BRAZING.
 2. FITTINGS LISTED FOR USE IN CONCEALED LOCATIONS.
  
 3) THE P3 NOTE 2 INDICATES SCHEDULE 40 METAL PIPE OR
 POLYEHTYLENE PLASTIC PIPE. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" ORITS EQUIVALENT
 BE USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2010 FUEL GAS SEC. 402.2
  