| 2014-05-09 10:58:44 | THE REISSUANCE APPLICATION HAS BEEN SUBMITTED WITH A |
| | CONTRACTOR IDENTIFIED AS EXEMPT FROM FS 489 LICENSING |
| | REQUIREMENTS. THE REMAINING SCOPE OF WORK FOR THE |
| | COMPLETION OF THIS PERMIT MAY NOT QUALIFY FOR THE |
| | EXEMPTION. PLEASE IDENTIFY EXACTLY WHICH EXEMPTION |
| | LISTED IN FS 489.103 IS APPLICABLE TO THIS APPLICATION. |
| | THE RECORD INDICATES SOME WORK WAS COMPLETED IN THE |
| | PAST, BUT ALONG WITH REVIEW OF THE ORIGINAL PLAN, A |
| | PLAN WITH REVISED DATE OF 10/17/13 HAS BEEN SUBMITTED. |
| | THE NEWER PLANS INDICATE ELECTRICAL AND PLUMBING WORK |
| | INCONSISTENT WITH THE ORIGINAL PLAN AS TO LOCATION. THE |
| | ORIGINAL ELECTRICAL AND PLUMBING SUB PERMITS WERE |
| | FINALED WITH THE ORIGINAL PLAN. HAS THE SINK LOCATION |
| | AND ELECTRICAL BEEN MOVED SINCE THE FINAL ELECTRICAL |
| | AND PLUMBING INSPECTIONS WERE PERFORMED? IF SO, NEW |
| | ELECTRICAL AND PLUMBING SUB PERMITS ARE REQUIRED, THE |
| | MACHANICAL SCOPE OF WORK HAS ALSO BEEN CHANGED IN THE |
| | REVISED PLAN. A REVISION SUBMITTAL OF THE |
| | AFOREMENTIONED CHANGES IS REQUIRED. SEE FBC 107.4 |
| | BELOW. ADDITIONAL FEES WILL APPLY. THE REVISED DRAWINGS |
| | SHOULD BE SUBMITTED AFTER THE PERMIT IS REISSUED. |
| | ALTERNATIVELY, A REVISION APPLICATION MAY BE SUBMITTED |
| | AT THIS TIME HOWEVER, ONE ADDITIONAL SET OF THE REVISED |
| | PLAN IS REQUIRED. |
| | |
| | FBC 107.4 AMENDED CONSTRUCTION DOCUMENTS. WORK SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE REVIEWED |
| | CONSTRUCTION DOCUMENTS, AND ANY CHANGES MADE DURING |
| | CONSTRUCTION THAT ARE NOT IN COMPLIANCE WITH |
| | THE REVIEWED CONSTRUCTION DOCUMENTS SHALL BE |
| | RESUBMITTED FOR REVIEW AS AN AMENDED SET OF |
| | CONSTRUCTION DOCUMENTS. |
| | |