| Notes |
| Date |
Text |
| 2014-06-09 10:44:37 | RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- BALANCED RETURN AIR IN MASTER BEDROOM: REVISE SIZE | | | OF TRANSFER GRILL TO COMPLY WITH EXCEPTION #2 OF SEC. | | | M1602.4. "THE TRANSFER GRILL SHALL USE 50 SQUARE INCHES | | | (OF GRILLE AREA) TO 100 CFM (OF SUPPLY AIR)". ALL THE | | | SUPPLY AIR INTO THE MASTER SUITE SHALL BE INCLUDED. | | | ACCORDING TO PLAN ON SHEET A3 ALL THE SUPPLY AIR TO THE | | | MASTER BEDROOM IS 377 CFM. THEREFORE, NEED A TRANSFER | | | GRILL WITH AT LEAST 188.5 SQUARE INCHES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|