2014-05-20 15:46:42ELECTRICAL PROVISOS FOR PERMIT 14041097
 1. AS PER NEC300.5(B), THE INTERIOR OF AN UNDERGROUND
 (OR IN CONCRETE SLAB) RACEWAY SHALL BE CONSIDERED A WET
 LOCATION; ALL CONDUCTORS WITHIN THE RACEWAY SHALL BE
 LISTED ACCORDINGLY.
 2. AS PER NEC 314.27, BOXES IN THE CEILING FOR HANGING
 LUMINARIES SHALL BE DESIGNED TO SUPPORT MINIMUM 50#.
 3. NEC 210.52, HAS SPECIFIC OUTLET SPACING
 REQUIREMENTS.
 4. SEE SUGGESTED 3WAY SWITCHING AS MARKED ON PLANS
  