| 2014-05-22 15:56:24 | BUILDING PLAN REVIEW |
| | PERMIT: 14041084 |
| | ADD: 4335 N HAVERHILL RD |
| | CONT:LENNAR HOMES, LLC |
| | TEL: (954)533-5299X1 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAY 22/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) STATE APPROVED PLANS INDICATE SITE INSTALLED ITEMS: |
| | 1A) STORM SHUTTERS |
| | 1B) ACCESSIBLE STAIRS AND RAMPS |
| | |
| | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(E) SHUTTERS |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION |
| | SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND |
| | MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC |
| | 1609.1.4. |
| | FL BLD CODE 2004 SECTION 106.3.3, 1609.1.4, 1714.5.1 & |
| | EXIST BUILD CODE 507.3. PROCEDURES: 1(B) A COMPLETE |
| | INSTALLATION SCHEDULE SUMMARIZING & IDENTIFYING OPENING |
| | SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT |
| | SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS, |
| | WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE |
| | SUBMITTED AT TIME OF PERMIT APPLICATION TO FACILITATE |
| | PLAN REVIEW AND PERMIT ISSUANCE. |
| | |
| | 5) 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | STAIRS CONSTRUCTION/GEOMETRY/ HANDRAILS/ GAURDRAILS |
| | 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: RAMPS/ HANDRAILS & GAURDRAILS. |
| | SITE REQUIREMENTS, ACCESSIBLE ROUTE & VERTICAL |
| | ACCESSIBILITY |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |