| Plan Review Notes For Permit 14041074 |
| Permit Number |
14041074 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-01 17:50:09 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. IMPACT PROTECTION REQUIRED, FBC 1609.1.4. | | | | | | EXITS CANNOT BE BLOCKED BY IMPACT PROTECTION | | | (SHUTTERS), SEE FBC 1003.6, MEANS OF EGRESS CONTINUITY. | | | | | | 2. ON THE PRODUCT APPROVAL, INDICATE OPTIONS PROPOSED. | | | THIS APPEARS TO BE AN ENTRY/EXIT DOOR, SO AN ACCESSIBLE | | | THRESHOLD IS REQUIRED FBC 2010 ACCESSIBILITY 404.2.5. | | | | | | 3. EITHER INDICATE ON THE PRODUCT APPROVAL WHERE PANIC | | | OR FIRE EXIT HARDWARE IS PROPOSED OR PROVIDE A LIFE | | | SAFETY PLAN WHICH SHOWS WHY THIS WOULD NOT BE REQUIRED, | | | FBC 1008.1.10. | | | | | | |
|