| Notes |
| Date |
Text |
| 2014-04-30 17:11:55 | PLEASE PROVIDE HP RATINGS OF ALL MOTORS. NEW AND OR | | | EXISTING. | | | PLEASE SHOW COMPLIANCE WITH THE NEC 430.32. MOTOR | | | OVERLOAD DEVICE TO BE PROVIDED FOR MOTORS OVER ONE HP. | | | A SEPARATE FIRE ALARM PERMIT IS REQUIRED. | | | THE PLANS INDICATE NEW FIRE ALARM DEVICES. PLEASE | | | PROVIDE COMPLETE F/A DRAWINGS TO INCLUDE A LOCATION OF | | | THE FACP, BATTERY CALCULATIONS. AND SUBMITTALS ON | | | EQUIPMENT. | | | THE PLANS INDICATE A EXISTING STANDBY GENERATOR. PLEASE | | | PROVIDE ADDITIONAL DETAIL ON THE GENERATOR SPECIFICALLY | | | HOW IT TIES INTO THE FACILITY'S ELECTRICAL SYSTEM. | | | | | | |
|