| Plan Review Notes For Permit 14041027 |
| Permit Number |
14041027 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-14 16:00:44 | DATE: 7/14/2014 | | | PROJECT: FOREVER 21 | | | PERMIT#: 14041027 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: PROVISO | | | | | | 2) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE | | | CONSIDERED A WET LOCATION. ALL CONDUCTORS INCLUDING LOW | | | VOLTAGE DATA/COM WITHIN THE RACEWAY SHALL BE LISTED | | | ACCORDINGLY. SUITABILITY FOR INSTALLATION AND USE IN | | | CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC | | | 110.3(A)(1 THRU 8) | | | | | | 3) A SEPARATE ELECTRICAL PERMIT APPLICATION ACCOMPANIED | | | BY SHOP DRAWINGS, BATTERY CALCULATIONS, AND EQUIPMENT | | | SUBMITTALS, SHALL BE SUBMITTED FOR ALL OF THE | | | FOLLOWING: | | | FIRE ALARM, SECURITY, CCTV, AND AUDIO/ VIDEO, NETWORK, | | | AND DATA/COM. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|