2014-07-14 16:00:44DATE: 7/14/2014
 PROJECT: FOREVER 21
 PERMIT#: 14041027
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 2) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS INCLUDING LOW
 VOLTAGE DATA/COM WITHIN THE RACEWAY SHALL BE LISTED
 ACCORDINGLY. SUITABILITY FOR INSTALLATION AND USE IN
 CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 3) A SEPARATE ELECTRICAL PERMIT APPLICATION ACCOMPANIED
 BY SHOP DRAWINGS, BATTERY CALCULATIONS, AND EQUIPMENT
 SUBMITTALS, SHALL BE SUBMITTED FOR ALL OF THE
 FOLLOWING:
 FIRE ALARM, SECURITY, CCTV, AND AUDIO/ VIDEO, NETWORK,
 AND DATA/COM.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]