| 2014-05-25 12:57:33 | PLUMBING PLAN REVIEW |
| | PERMIT: 14041027 |
| | ADD: 1795 PALM BEACH LAKES BLVD # W401 |
| | CONT: TBD |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUN AY 25/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) NO INDEX OF PLANS AND NO PLUMBING DRAWINGS LABELED |
| | IN THE SET OF PLANS. PLUMBING RELATED REVIEW FOUND |
| | UNDER M1.3.0. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE |
| | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| | CRITERIA AND DOCUMENTS:107.3.5.1 COMMERCIAL BUILDINGS, |
| | 107.3.5.1.3 PLUMBING |
| | 1. MINIMUM PLUMBING FACILITIES |
| | 2. FIXTURE REQUIREMENTS |
| | 3. WATER SUPPLY PIPING |
| | 4. SANITARY DRAINAGE |
| | 5. WATER HEATERS |
| | |
| | NOT UNDER MECHANICAL. |
| | |
| | 2) SHEET M1.3.0 DETAIL #5 SHOWS A TRAP PRIMER BUT UNDER |
| | THE PLUMBING FIXTURE AND EQUIPMENT SCHEDULE NEITHER THE |
| | FLOOR DRAIN OR TRAP SEAL PRIMER IS LISTED. |
| | SHOW COMPLIANCE WITH 2010 FBC-PLUMBING 1002.2 & 1002.4. |