| Notes |
| Date |
Text |
| 2014-05-19 16:16:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | SHEET AO.1.5 - PLEASE REVIEW THE LOCATION OF THE FIRE | | | EXTIGUISHERS TO ENSURE COMPLIANCE WITHIN 75'. A FIRE | | | INSPECTOR WILL VERIFY LOCATIONS ON FIRE INSPECTION. | | | | | | SHEET 3.0.1 - PLEASE INSTALL A ROOF LIGHTWEIGHT TRUSS | | | SIGN. NOTICE IS REQUIRED FOR STRUCTURES WITH | | | LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, | | | INDUSTRIAL, OR ANY MULTIUNIT RESIDENTIAL STRUCTURE OF | | | THREE UNITS OR MORE WHICH USES HORIZONTAL OR VERTICAL | | | LIGHT-FRAME TRUSS-TYPE CONSTRUCTION IN ANY PORTION | | | SHALL BE MARKED WITH AN APPROVED SYMBOL. THE APPROVED | | | SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO THE LEFT OF | | | THE MAIN ENTRY DOOR. A FIRE INSPECTOR WILL VERIFY ON | | | FIRE INSPECTION. | | | | | | SHEET H2 - PLEASE INSTALL LETTERING TO READ "BY ORDER | | | OF THE FIRE DEPARTMENT" FOR FIRE LANE NO PARKING SIGN. | | | A FIRE INSPECTOR WILL VERIFY ON FIRE INSPECTION. |
|