2014-05-25 11:41:54BUILDING PLAN REVIEW
 PERMIT: 14041027
 ADD: 1795 PALM BEACH LAKES BLVD # W401
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN AY 25/ 2014
 ACTION: DENIED
  
 1) PLEASE CORRECT THE ADDRESS ON BOTH THE PERMIT
 APPLICATION AND NONE PROVIDED ON THE PLANS. SHEET A0.00
 THE KEY PLAN IDENTIIES THE LOCATION OF THE PROJECT
 WITHIN THE PALM BEACH OUTLET MALL AS BUILDING J2. THE
 CORRECT ADDRESS FOR THIS BUILDING IS 1795 PALM BEACH
 LAKES BLVD # W401.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED.
  
 2010 FBC-B [F] 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS NUMBERS OR LETTERS.
  
 2) FOR THE TENANT BUILD-OUT CONTRACTOR TO START WORK
 BEFORE THE SHELL CONTRACTOR RECEIVES THEIR CERTIFICATE
 OF COMPLITION PLEASE REVIEW THE FOLLOWING REQUIREMENT.
 PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER .
 PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITH SUITE
 NUMBER WITHIN THE DOCUMENT.
  
 TRACY BECKER, TENANT COORDINATOR
 [email protected]
 618-514-2128
  
 3) THE COVERSHEET A0.00 OCCUPANT LOAD COUNT DOES NOT
 ROLL UP TO THE NEXT WHOKE NUMBER THEIR CAN NOT BE PARTS
 OF AN OCCUPANT. 2010 FBC-B 1004.1 SEE BOAF INFORMAL
 INTERPRETATION 5479 NOTICE: THE BUILDING OFFICIALS
 ASSOCIATION OF FLORIDA, IN COOPERATION WITH THE FLORIDA
 BUILDING COMMISSION, THE FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS, ICC, AND INDUSTRY AND PROFESSIONAL
 EXPERTS OFFER THIS INTERPRETATION OF THE FLORIDA
 BUILDING CODE IN THE INTEREST OF CONSISTENCY IN THEIR
 APPLICATION STATEWIDE. THIS INTERPRETATION IS INFORMAL,
 NON-BINDING AND SUBJECT TO ACCEPTANCE AND APPROVAL BY
 THE LOCAL BUILDING OFFICIAL.
  
 4) SHEET A0.15 EGRESS PLAN / LIFE SAFETY PLAN
 4A) NOTE ON THE PLANS ABOUT EXIT NUMBER 3, NO EXITS ARE
 IDENTIFIED AS 1, 2 OR 3. THE OCCUPANT LOAD IS 474, X
 0,2 (FBC-B1005.1) = 94.8 INCHES OF REQUIRED EGRESS
 OPENINGS, PLEASE SHOW COMPLIANCE WITH ; 1015.2.1 TWO
 EXITS OR EXIT ACCESS DOORWAYS. EXCEPTIONS: 2. WHERE A
 BUILDING IS EQUIPPED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1
 OR 903.3.1.2, THE SEPARATION DISTANCE OF THE EXIT DOORS
 OR EXIT ACCESS DOORWAYS SHALL NOT BE LESS THAN
 ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE AREA SERVED.
 WHERE DOES THE 0.15 COME FROM.
  
 4B) COMPLIED.
  
 4C) (1)THE LIFE SAFETY / EGRESS PLAN DOES NOT PROVIDE A
 FURNITURE, KIOSK, COUNTER AAND TABLE LAYOUT OF THE
 MERCANTILE OCCUPANCY INCLUDING DRESSING ROOMS, STOCK
 ROOM,
 RESTROOM AND CORRIDORS PLEASE PROVIDE SUCH A LAYOUT AND
 SHOW EXIT SIGNS AND DIRECTIONAL IN ACCORDANCE WITH:
 2010 FBC-B 1006.3.1
 EXITS SHALL BE MARKED BY AN APPROVED SIGN READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. EVERY EXIT
 SIGN SHALL BE SUITABLY ILLUMINATED BY A RELIABLE LIGHT
 SOURCE. EXTERNALLY AND INTERNALLY ILLUMINATED SIGNS
 SHALL BE VISIBLE IN BOTH NORMAL AND EMERGENCY LIGHTING.
  
 4C)(2)1006.3.8
 WHERE THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT
 IS NOT APPARENT, A DIRECTIONAL SIGN COMPLYING WITH
 SECTIONS 1006.3.5 OR 1006.3.6 READING ?EXIT,? OR A
 SIMILAR DESIGNATION WITH A DIRECTIONAL INDICATOR
 SHOWING THE DIRECTION OF TRAVEL SHALL BE PLACED IN
 EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE LISTED.
  
 4C)(3) 1006.3.4 EXIT STAIR DOOR OR TACTILE SIGNAGE.
 TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH
 ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 5) SHEETH2 SHOWS A HIGH/ LOW DRINKING FOUNTAIN AND THEN
 2 SINGLE DRINKING FOUNTAINS WITH OUT DETAIL NUMBERS ,
 THERE IS EXTENSION LINES BUT NO INFORMATION AS TO
 CONFORMITY TO THE 2010 FL ACCESSIBILITY CODE, IF SHOWN
 ON THE PLAN THEY WILL NEED TO SHOW COMPLIANCE WITH 2010
 FL ACCESSIBILITY CODE 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 6) IF IN TTHE PLANS I DIDN'T SEE COMPLIANCE WITH 2010
 FL ACCESSIBILITY CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  