| Plan Review Notes For Permit 14041022 |
| Permit Number |
14041022 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-13 07:45:04 | 1ST REVIEW: | | | | | | PROVIDE DESIGN WIND LOAD REQUIREMENTS USING ASCE-7 | | | STANDARD AS OUTLINED IN STEP 1 ON SHEET 3 OF 10 IN NOA | | | 13-1021.07. | | | | | | PROVIDE A SITE SPECIFIC DRAWING WITH DIMENSIONS TO | | | DETERMINE THE HEIGHT, WIDTH, AND MULLION SPACING FOR | | | THE SYSTEM. | | | | | | THE PHOTOGRAPH PROVIDED INDICATE MULLION SPACING OF | | | 39". THE HIGHLIGHTED OR SLECTED DESIGN IS BASED ON 32" | | | NOMINAL WIDTH. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | | | | |
|