| Plan Review Notes For Permit 14040982 |
| Permit Number |
14040982 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2015-02-03 15:38:41 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. TWO SETS REQUIRED, FBC 107. | | | | | | 2. PRESSURES PROPOSED IS +-120PSF. THIS IS TOO HIGH; | | | PLEASE REVISE TO -47 (THE LOWEST ON THE PRODUCT | | | APPROVAL WHICH YOU SUBMITTED). IT IS NOT CLEAR WHY A | | | DESIGN PRESSURE WHICH EXCEEDS PRESSURES FOR HIGH RISES | | | WOULD BE USED AS CRITERIA FOR A ONE STORY STRUCTURE. | | | | | | 3. SEE SHEET 11 OF THE PRODUCT APPROVAL. HOLLOW BLOCK | | | SUBSTRATE, C4 CONNECTION, REQUIRES 3.4" SPACING UP TO | | | 6', AND ITW TAPCON, C4 CONNECTION NOT ALLOWED FOR SPAN | | | OVER 6'. | | | | | | 4. SEE THE PRODUCT APPROVAL SUBMITTED, PAGE 8. IT | | | APPEARS THAT C4 IS A FLOOR MOUNT. HOW COULD A FLOOR | | | MOUNT BE USED FOR WINDOWS? I CANNOT DETERMINE WHICH | | | CONNECTION TYPE YOU SELECTED BASED ON THE PHOTOGRAPHS | | | PROVIDED (APPEARW THAT IT MAY BE A C2 CONNECTION), BUT | | | IT DOES NOT APPEAR TO BE A FLOOR MOUNT WHICH IS | | | TYPICALLY USED AT DOORS. | | | | | | |
|