| 2014-09-11 14:19:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | FROM PREVIOUS LIST: | | | | | | 1. COMPLETE THE FOLLOWING INFORMATION ON THE | | | INSTALLATION SCHEDULE: | | | | | | SHUTTER MOUNTING CONNECTION TYPE (SHOULD CORRELATE WITH | | | THE ANCHOR SHEETS ON SHEET 11) | | | | | | THIS WAS NOT COMPLETED. SOMETHING WAS WRITTEN, BUT IT | | | IS ILLEGIBLE. THIS SHOULD CORRELATE WITH THE ANCHOR | | | CHART, WHICH USES THE NAMING CONVENTION C1, C2, C3, C4, | | | AND C5. SO, THIS COLUMN SHOULD INCLUDE THESE ANCHOR | | | CONNECTION TYPES. | | | | | | SUBSTRATE (TYPICALLY CONCRETE TOP, BLOCK BOTTOM, BUT | | | SOMETIMES BLOCK TOP AND BOTTOM) | | | | | | 2ND REVIEW, CONCRETE SPECIFIED. THIS IS MOST LIKELY NOT | | | THE CASE, MOST LIKELY CONCRETE TOP, BLOCK BOTTOM. | | | | | | AS SPANS ARE SMALL, THE "WORST CASE" WOULD BE A C4 | | | CONNECTION, HOLLOW BLOCK, 3.4" ANCHOR SPACING. EITHER | | | REVISE INSTALLATION SCHEDULE TO INCLUDE ALL INFORMATION | | | REQUIRED TO DEMONSTRATE CODE COMPLIANCE OR CHANGE | | | ANCHOR SPACING TO WORST CASE CONDITIONS (3.4"). | | | | | | 2ND REVIEW, ANCHOR SPACING NOW PROPOSES 24" ON THE | | | BOTTOM WHICH DOES NOT COMPLY FOR ANY OF THE ANCHOR | | | TYPES. | | | | | | 2. ANCHOR PROPOSED IS NOW "WEDGE." THIS IS NOT ONE OF | | | THE APPROVED FASTENERS IN THE PRODUCT APPROVAL. | | | | | | |
|