2014-05-15 17:31:15****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 1. COMPLETE THE FOLLOWING INFORMATION ON THE
 INSTALLATION SCHEDULE:
  
 SHUTTER MOUNTING CONNECTION TYPE (SHOULD CORRELATE WITH
 THE ANCHOR SHEETS ON SHEET 11)
 SUBSTRATE (TYPICALLY CONCRETE TOP, BLOCK BOTTOM, BUT
 SOMETIMES BLOCK TOP AND BOTTOM)
  
 AS SPANS ARE SMALL, THE "WORST CASE" WOULD BE A C4
 CONNECTION, HOLLOW BLOCK, 3.4" ANCHOR SPACING. EITHER
 REVISE INSTALLATION SCHEDULE TO INCLUDE ALL INFORMATION
 REQUIRED TO DEMONSTRATE CODE COMPLIANCE OR CHANGE
 ANCHOR SPACING TO WORST CASE CONDITIONS (3.4").
  