| Plan Review Notes For Permit 14040969 |
| Permit Number |
14040969 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-29 17:55:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. EGRESS IS SHOWN AS A SCREEN INSTALLED OVER AN | | | OUTSWING DOOR. PROVIDE A DETAIL TO SHOW HOW THE DOOR | | | WILL OPERATE WITH THE SHUTTER INSTALLED. INSTALLATION | | | SCHEDULE INDICATES THAT THE SHUTTER GLASS SEPARATION IS | | | 0. SEE FBC 2010 RESIDENTIAL 310.4. | | | | | | 2. SPANS NOT CLEAR. FOR INSTANCE, SEE OPENING 1. A | | | 40X66 (WXH), VERTICAL INSTALLATION, 4" EDGE DISTANCE, | | | SHOULD HAVE A SPAN BETWEEN 66" AND 74", DEPENDING ON | | | INSTALLATION METHOD, BUT SPAN IS 40" ON THE | | | INSTALLATION SCHEDULE. SHUTTER MOUNTING CONNECTION TYPE | | | IS NOTED AS "TYPICAL", BUT "TYPICAL" IN THE PRODUCT | | | APPROVAL INCLUDES MANY DIFFERENT OPTIONS. REVISE SPANS | | | AND PROVIDE MORE SPECIFIC INFORMATION IF NECESSARY. | | | | | | 3. FASTENER PROPOSED NOT CLEAR. SEE PAGE 2; FOUR | | | DIFFERENT TYPES OF LAGS WITH DIFFERENT LIMITATIONS. | | | REVISE FASTENER TO BE SPECIFIC AS TO WHICH OF THE FOUR | | | LAGS IS PROPOSED. | | | | | | 4. EDGE DISTANCE IS 4", FOR WOOD, NOT CLEAR IF THIS IS | | | POSSIBLE. THIS WOULD REQUIRE 8" OF STRUCTURAL WOOD | | | SUBSTRATE, TOP AND BOTTOM, BUT THIS IS NOT TYPICAL OF | | | WOOD FRAME STRUCTURES. PLEASE CLARIFY OR REVISE. | | | | | | | | | |
|