| Plan Review Notes For Permit 14040949 |
| Permit Number |
14040949 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-05-02 10:08:13 | THIS PERMIT FAILED THE ELECTRICAL REVIEW AS FOLLOWS: | | | 1. IT FAILED TO SHOW THE DISCONNECT REQUIRED PER NEC | | | 600.6 | | | 2. IF FAILS TO INCLUDE THEE GROUNDING AS REQUIRED PER | | | NEC 600.7 | | | 3. IT FAILS TO INDICATE COMPLIANCE WITH THE FBC-ENERGY | | | CONSERVATION SECTION 505. | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | | | | | | 2014-05-02 09:50:24 | SECOND REVIEW STOP WAS ADDED BECAUSE SYSTEM LOCKED | | | RESTRICTING ACCESS TO THE PREVIOUS ACTIVE E STOP. |
|