| Plan Review Notes For Permit 14040933 |
| Permit Number |
14040933 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-28 09:34:16 | FBC 107.3.5.1.2 STATES: | | | "WIRING, SERVICES, FEEDERS AND BRANCH CIRCUITS, | | | OVERCURRENT PROTECTION, GROUNDING, WIRING METHODS AND | | | MATERIALS, GFCI?S, EQUIPMENT, SPECIAL OCCUPANCIES, | | | EMERGENCY SYSTEMS, COMMUNICATION SYSTEMS, LOAD | | | CALCULATIONS, AND DESIGN FLOOD ELEVATION." | | | | | | PLEASE PROVIDE THE FOLLOWING IN ADDITION TO THE PLANS | | | SUBMITTED.: | | | A RISER DIAGRAM OF THE ELECTRICAL SERVICE INDICATING | | | THE PANELS USED IN THIS INSTALLATION. | | | PANEL SCHEDULES FOR THE AFFECTED PANELS INDICATING THE | | | NEW CIRCUITS. | | | LOAD CALCULATIONS INDICATING THE AVAILABLE CIRCUIT AND | | | LOAD CAPACITY FOR THE AFFECTED PANELS AND THE THE | | | CAPCITY ON THE SERVICE FOR THE INCREASED LOAD ON THE | | | SERVICE MAIN(S). |
|