| Plan Review Notes For Permit 14040928 |
| Permit Number |
14040928 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-25 17:46:29 | RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: 2010 FBC. | | | | | | 1- NOA 12-0625.02 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE. NEED CURRENT NOA. VISIT THE MIAMI-DADE | | | WEBSITE AND DOWNLOAD CURRENT NOA. DCA RULE 9N-3. | | | | | | 2- PROVIDE FIELD WITHDRAWAL RESISTANCE TEST (TAS 105) | | | AS REQUIRED BY GENERAL LIMITATION #5 AND #6 ON LAST | | | PAGE OF NOA SUBMITTED. SEC. 1609 FBC. | | | | | | 3- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2 | | | COPIES) AS REQUIRED BY GENERAL LIMITATION #7 ON LAST | | | PAGE OF NOA SUBMITTED. SEC. 1609 FBC. | | | | | | ***NOTE: ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE | | | PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICE | | | (561)805-6712 |
|