2014-04-30 13:42:26PLUMBING PLAN REVIEW
 PERMIT: 14040925
 ADD: 4158 LAKE TAHOE CIR
 CONT: LSCI, INC.
 TEL: (727)571-4141
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 30/ 2014
 ACTION: DENIED
  
 1) THE DETAIL SHEET FOR THE WATER HEATER IS MISSING THE
 INFORMATION ON THE REQUIREMENTS FOR DISCHARGE PIPING.
 2010 FBC-P 504.6 REQUIREMENTS FOR DISCHARGE PIPING.
 THE DISCHARGE PIPING SERVING A PRESSURE RELIEF VALVE,
 TEMPERATURE RELIEF VALVE OR COMBINATION THEREOF SHALL:
  
 1. NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM.
  
 2. DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER.
  
 3. NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF
 THE VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE
 AIR GAP.
  
 4. SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT
 TO PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT.
  
 5. DISCHARGE TO THE FLOOR, TO THE PAN SERVING THE WATER
 HEATER OR STORAGE TANK, TO A WASTE RECEPTOR OR TO THE
 OUT-DOORS.
  
 6. DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL
 INJURY OR STRUCTURAL DAMAGE.
  
 7. DISCHARGE TO A TERMINATION POINT THAT IS READILY
 OBSERVABLE BY THE BUILDING OCCUPANTS.
  
 8. NOT BE TRAPPED.
  
 9. BE INSTALLED SO AS TO FLOW BY GRAVITY.
  
 10. NOT TERMINATE MORE THAN 6 INCHES (152 MM) ABOVE THE
 FLOOR OR WASTE RECEPTOR.
  
 11. NOT HAVE A THREADED CONNECTION AT THE END OF SUCH
 PIPING.
  
 12. NOT HAVE VALVES OR TEE FITTINGS.
  
 13. BE CONSTRUCTED OF THOSE MATERIALS LISTED IN SECTION
 605.4 OR MATERIALS TESTED, RATED AND APPROVED FOR SUCH
 USE IN ACCORDANCE WITH ASME A112.4.1.
  
 SECTION 612
 SOLAR SYSTEMS
  
 2) 2010 FBC-R M612.1 SOLAR SYSTEMS.
 THE CONSTRUCTION, INSTALLATION, ALTERATIONS AND REPAIR
 OF SYSTEMS, EQUIPMENT AND APPLIANCES INTENDED TO
 UTILIZE SOLAR ENERGY FOR SPACE HEATING OR COOLING,
 DOMESTIC HOT WATER HEATING, SWIMMING POOL HEATING OR
 PROCESS HEATING SHALL BE IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL .
 M2301.5 BACKFLOW PROTECTION.
 CONNECTIONS FROM THE POTABLE WATER SUPPLY TO SOLAR
 SYSTEMS SHALL COMPLY WITH SECTION P2902.5.5.
 P2902.5.5 SOLAR SYSTEMS.
 THE POTABLE WATER SUPPLY TO A SOLAR SYSTEM SHALL BE
 EQUIPPED WITH A BACKFLOW PREVENTER WITH INTERMEDIATE
 ATMOSPHERIC VENT COMPLYING WITH ASSE 1012 OR A REDUCED
 PRESSURE PRINCIPLE BACKFLOW PREVENTER COMPLYING WITH
 ASSE 1013. WHERE CHEMICALS ARE USED, THE POTABLE WATER
 SUPPLY SHALL BE PROTECTED BY A REDUCED PRESSURE
 PRINCIPLE BACKFLOW PREVENTER.
  
 EXCEPTION: WHERE ALL SOLAR SYSTEM PIPING IS A PART OF
 THE POTABLE WATER DISTRIBUTION SYSTEM, IN ACCORDANCE
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 PLUMBING, AND ALL COMPONENTS OF THE PIPING SYSTEM ARE
 LISTED FOR POTABLE WATER USE, CROSS-CONNECTION
 PROTECTION MEASURES SHALL NOT BE REQUIRED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  