Plan Review Notes
Plan Review Notes For Permit 14040925
Permit Number 14040925
Review Stop B
Sequence Number 1
Notes
Date Text
2014-04-30 12:25:57BUILDING PLAN REVIEW
 PERMIT: 14040925
 ADD: 4158 LAKE TAHOE CIR
 CONT: LSCI, INC.
 TEL: (727)571-4141
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. APRIL 30/ 2014
 ACTION: DENIED
  
 1) THE PLANS SHEET A.1.3-10 HAVE A GENERIC ROOF DETAIL
 THAR INDICATES THAT IT SHOULD NOT BE INSTALLED IN A
 ROOF ZONE 3. PLEASE PROVIDE A ROOFING PLAN TO SCALE TO
 SHOW THE SIZE OF THE ROOF AND WHERE THE INSTALATION OF
 THE SOLAR COLECTOR WILL BE LOCATED. PLEASE IDENTIFY THE
 ROOF ZONES 1, 2 & 3.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES
 AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL...
  
 2) THROUGHOUT THE PLAN IT MAKES REFERANCE TO OPTIONS
 FROM THE TYPE OF FASTENER, TO THE FRAMING DETAILS, TO
 THE TYPE OF MOUNTING BRAKETS TO THE TILT KIT DECK
 ANCHOR. THE PLANS NEED TO BE SPECIFIC IN NATURE AS TO
 THE INSTALATION, CIRCLE OR IDENTIFY EACH TYPE OF OPTION
 SO THEY PLAN WILL BE SPECIFIC TO THIS INSTALATION.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 3) THE WEBSITE LISTED ON THE PLANS FOR VERIFICATION OF
 THE WIND LOAD CALCULATIONS WOULD NOT OPEN, CALCULATIONS
 COULD NOT BE VERIFIED.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676