| Plan Review Notes For Permit 14040885 |
| Permit Number |
14040885 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-29 07:09:36 | BUILDING PROVISO: | | | PLEASE COMPLY WITH: | | | 1) 2010 FBC-BUILDING 1404.2.1 | | | WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH | | | OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO | | | PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE | | | WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED | | | BETWEEN THE WATER RESISTIVE BARRIER AND THE CEMENT | | | PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING: | | | 1.1. TWO LAYERS OF AN APPROVED WATER RESISTANT BARRIER | | | OR | | | 1.2. ONE LAYER OF AN APPROVED WATER RESISTANT BARRIER | | | OVER AN APPROVED PLASTIC HOUSE WRAP, OR | | | 1.3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN | | | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS. | | | | | | 2) 1503.3 COPING. | | | PARAPET WALLS SHALL BE PROPERLY COPED WITH | | | NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A WIDTH NO | | | LESS THAN THE THICKNESS OF THE PARAPET WALL. | | | | | | | | | |
|