| 2014-05-21 12:03:49 | PLUMBING PLAN REVIEW |
| | REVISION: 14040884 |
| | PERMIT: 13120972 |
| | ADD: 5802 S DIXIE HWY. |
| | CONT: MIKE MOORE |
| | TEL: (561)301-9468 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WEDNESDAY MAY 21/2014 |
| | ACTION: PROVISO |
| | |
| | 1) THIS IS A EXPANSION OF A INTERIOR- DEMO PERMIT TO |
| | INCLUDE THE REBUILDING OF A RESTROOM, THIS TENANT SPACE |
| | IS TO BE CONSIDERED A SHELL OR VANILLA BOX .PLEASE NOTE |
| | THE REQUIREMENTS FOR THE FOLLOWING OCCUPANCIES FOR A |
| | FUTURE TENANT BUILD OUT: |
| | . NOTE TENANT SPACE IS APPROXIMATELY 1386 SQ FT. |
| | BUSINESS 1386 SQ FT/ 100= 14 OCCUPANT LOAD 2010 FBC-P |
| | 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX |
| | |
| | MERCANTILE 1386 SQ FT / 30 = 47 OCCUPANT LOAD 2010 |
| | FBC-P 403.2 EXC 3 ALLOWS FOR A SINGLE UNISEX & HI-LOW |
| | DRINKING FOUNTAIN. |
| | |
| | MERCANTILE (RESTUARANT , 50 OCC) 1386 SQ FT / 30 = 47 |
| | OCCUPANT LOAD 2010 FBC-P 403.2 EXC 3 ALLOWS FOR A |
| | SINGLE UNISEX, SERVICE SINK & GREASE INTERCEPTOR SIZED |
| | FOR FLOW RATE |
| | |
| | RESTAURANT 1386 SQ FT/ 15= 93 OCCUPANT LOAD REQUIRING 2 |
| | RESTROOMS, SERVICE SINK & GREASE INTERCEPTORSIZED FOR |
| | FLOW RATE. |
| | |
| | JAMES A. WITMER CBO |