| Date |
Text |
| 2014-07-09 15:28:40 | DATE: 7/9/2014 |
| | PROJECT: SEABOARD TRAIN STATION. |
| | PERMIT#: 14040876 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 |
| | SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT |
| | OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & |
| | TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME |
| | SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING |
| | DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E |
| | 505.2.4 |
| | |
| | 2) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL |
| | BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO |
| | THE WEATHER-PROOF COVERS. NEC 406.8(B) |
| | ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1) |
| | THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER |
| | PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS. |
| | |
| | 3) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE |
| | CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE |
| | RACEWAY SHALL BE LISTED ACCORDINGLY. |
| | SUITABILITY FOR INSTALLATION AND USE SHALL BE IN |
| | CONFORMITY WITH THE PROVISIONS OF |
| | THIS CODE. NEC 110.3(A)(1 THRU 8) |
| | |
| | 4)THE PROVISIONS OF PART I AND PART V OF THE NEC |
| | ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED |
| | FOUNTAINS AS DEFINED IN 680.2. NEC 680.50 |
| | THE LIGHTING AND SUBMERSIBLE PUMP CIRCUITS SHALL BE |
| | GFCI PROTECTED UNLESS THEY OPERATE AT UNDER 15 VAC. NEC |
| | 680.51 |
| | |
| | 5) WIND LOADS SHALL BE DETERMINED IN ACCORDANCE WITH |
| | CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF |
| | THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR AT [email protected] |
| | |