Plan Review Notes
Plan Review Notes For Permit 14040876
Permit Number 14040876
Review Stop E
Sequence Number 2
Notes
Date Text
2014-07-09 15:28:40DATE: 7/9/2014
 PROJECT: SEABOARD TRAIN STATION.
 PERMIT#: 14040876
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 2) THE "WP" RECEPTACLE ADJACENT TO THE FOUNTAIN SHALL
 BE LISTED "WR" WEATHER-RESISTANT TYPE IN ADDITION TO
 THE WEATHER-PROOF COVERS. NEC 406.8(B)
 ALL 125-VOLT, SINGLEPHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (5) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL: NEC 210.8(B)(4) OUTDOORS.
  
 3) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY.
 SUITABILITY FOR INSTALLATION AND USE SHALL BE IN
 CONFORMITY WITH THE PROVISIONS OF
 THIS CODE. NEC 110.3(A)(1 THRU 8)
  
 4)THE PROVISIONS OF PART I AND PART V OF THE NEC
 ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED
 FOUNTAINS AS DEFINED IN 680.2. NEC 680.50
 THE LIGHTING AND SUBMERSIBLE PUMP CIRCUITS SHALL BE
 GFCI PROTECTED UNLESS THEY OPERATE AT UNDER 15 VAC. NEC
 680.51
  
 5) WIND LOADS SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF
 THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]
  