2014-05-07 20:14:03FIRST ELECTRICAL REVIEW FAILED AS BELOW INDICATED:
  
 1. MISSING A SECOND SET OF PLANS FOR APPROVAL
  
 2. MISSING THE WIND LOAD CALCS FOR THE POLES WITH THE
 RESPECTIVE FIXTURE HEADS. THESE WIND LOAD CALCS SHALL
 COMPLY WITH THE "LIGHT POLE NOTES" OF PAGE E1.03
  
 3 AS PER NEC 680.51, THE LIGHTING AND SUBMERSIBLE PUMP
 CIRCUITS SHALL BE GFCI PROTECTED UNLESS THEY OPERATE AT
 UNDER 15 VAC.
  
 4. AS PER NEC 406.8(B) THE "WP" RECEPTACLE ADJACENT TO
 THE FOUNTAIN SHALL BE LISTED "WR" WEATHER-RESISTANT
 TYPE IN ADDITION TO THE WEATHER-PROOF COVERS.
  