| Plan Review Notes For Permit 14040876 |
| Permit Number |
14040876 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-07 20:14:03 | FIRST ELECTRICAL REVIEW FAILED AS BELOW INDICATED: | | | | | | 1. MISSING A SECOND SET OF PLANS FOR APPROVAL | | | | | | 2. MISSING THE WIND LOAD CALCS FOR THE POLES WITH THE | | | RESPECTIVE FIXTURE HEADS. THESE WIND LOAD CALCS SHALL | | | COMPLY WITH THE "LIGHT POLE NOTES" OF PAGE E1.03 | | | | | | 3 AS PER NEC 680.51, THE LIGHTING AND SUBMERSIBLE PUMP | | | CIRCUITS SHALL BE GFCI PROTECTED UNLESS THEY OPERATE AT | | | UNDER 15 VAC. | | | | | | 4. AS PER NEC 406.8(B) THE "WP" RECEPTACLE ADJACENT TO | | | THE FOUNTAIN SHALL BE LISTED "WR" WEATHER-RESISTANT | | | TYPE IN ADDITION TO THE WEATHER-PROOF COVERS. | | | | | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | | CONTACT: | | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | PH: (561) 805-6718, EMAIL: [email protected] | | | | | | |
|