| 2014-04-25 06:52:20 | BUILDING PLAN REVIEW |
| | PERMIT: 14040858 |
| | ADD: 300 S AUSTRALIAN AVE, SUITE # 1105 |
| | CONT: T. H. MOTTLEY CONST. |
| | TEL: (561)502-1986 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 1ST REVIEW |
| | DATE: FRIDAY, APRIL 25/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE PERMIT APPLICATION INDICATES UNDER THE SCOPE OF |
| | WORK TO INSTALL LAMINATE FLOORING WITH ECO ULTRA QUIET |
| | FOAM UNDER LAYMENT. PLEASE PROVIDE COMPLIANCE WITH: |
| | EXCEPTION # 3. |
| | 1A) 2010 FBC-B: SECTION 603 |
| | COMBUSTIBLE MATERIAL IN TYPE I |
| | AND II CONSTRUCTION |
| | |
| | 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM |
| | PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 25. |
| | EXCEPTIONS: |
| | 1. INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26. |
| | |
| | 2) THE SUBMITTED SOUND REPORT WAS TESTED TO THE WRONG |
| | STANDARD. |
| | 2010 FBC-B: SECTION 603 |
| | COMBUSTIBLE MATERIAL IN TYPE I & II |
| | AND II CONSTRUCTION |
| | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES |
| | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A |
| | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE |
| | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS |
| | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 492. |
| | |