| 2014-05-06 17:18:26 | 6801 NORTH JOG ROAD - NURSE TRAILER |
| | PERMIT #14040855 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | INDENTIFICATION (NAME, ADDRESS, LETTER) VISIBLE FROM |
| | THE STREET. CHARACTERS SHALL BE ATTACHED TO THE |
| | BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH |
| | 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND. |
| | |
| | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT |
| | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, |
| | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN |
| | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER |
| | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR |
| | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT |
| | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH |
| | DIAMETER SPHERE. |
| | |
| | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. |
| | HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND |
| | NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, |
| | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| | LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE |
| | RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| | 2 INCHES. |
| | |
| | STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN |
| | HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A |
| | MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE |
| | ACCUMULATION OF WATER. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |