Plan Review Notes
Plan Review Notes For Permit 14040803
Permit Number 14040803
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-28 17:10:38ELECTRICAL PROVISO FOR PERMIT 14040803
  
 1. FOR FINAL INSPECTION THIS SYSTEM SHALL UNDERGO A
 REACCEPTANCE TEST AS PER NFPA 72, SECTION 10.4.1.2.
 RECORDS OF SUCH SHALL BE KEPT IN THE SYSTEM LOG AS
 REQUIRED.
 2. PER NFPA 72, SECTION 4.4, THE DEDICATED FIRE ALARM
 CIRCUIT BREAKER SHALL BE MARKED IN RED AND IDENTIFIED
 AS ?FIRE ALARM CIRCUIT? AND BE MECHANICALLY PROTECTED.
  