| Plan Review Notes For Permit 14040798 |
| Permit Number |
14040798 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-07-09 11:55:47 | DATE: 7/9/2014 | | | PROJECT: COURTNEY LAKES FOUNTAIN | | | PERMIT#: 14040798 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 3RD ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | DUPLICATE COMMENTS: | | | | | | 1) THE PROVISIONS OF PART I AND PART V OF THE NEC | | | ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED | | | FOUNTAINS AS DEFINED IN 680.2. NEC 680.50 | | | | | | 2) INDICATE ON THE PLANS A SINGLE LINE DIAGRAM, | | | GROUNDING DETAILS, LOAD CALCULATION, AND PANEL SCHEDULE | | | INDICATING THE AVAILABILITY OF THE CIRCUITRY AND | | | AMPACITY FOR THE INSTALLATION OF THE NEW EQUIPMENT | | | LOADS. NEC 680.6 & FBC 107.2.1 | | | | | | 3) INDICATE ON A SITE PLAN THE LOCATION OF THE | | | CIRCULATION PUMP AND DISCONNECTING MEANS, LED DRIVER, | | | AND THE SWITCHGEAR PROVIDING THE ELECTRICAL CIRCUITRY. | | | NEC 680.12, FBC 107.2.1 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR AT [email protected] |
|