Plan Review Notes
Plan Review Notes For Permit 14040797
Permit Number 14040797
Review Stop E
Sequence Number 2
Notes
Date Text
2014-06-24 17:02:25DATE: 6/24/2014
 PROJECT: COURTNEY LAKES FOUNTAIN
 PERMIT#: 14040797
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PLEASE REVISE AND RESUBMIT THE PLANS WITH THE FOLLOWING
 INFORMATION:
  
 1) THE PROVISIONS OF PART I AND PART V OF THE NEC
 ARTICLE 680 SHALL APPLY TO ALL PERMANENTLY INSTALLED
 FOUNTAINS AS DEFINED IN 680.2. NEC 680.50
  
 2) INDICATE ON THE PLANS A SINGLE LINE DIAGRAM,
 GROUNDING DETAILS, LOAD CALCULATION, AND PANEL SCHEDULE
 INDICATING THE AVAILABILITY OF THE CIRCUITRY AND
 AMPACITY FOR THE INSTALLATION OF THE NEW EQUIPMENT
 LOADS. NEC 680.6 & FBC 107.2.1
  
 3) INDICATE ON A SITE PLAN THE LOCATION OF THE
 CIRCULATION PUMP AND DISCONNECTING MEANS, LED DRIVER,
 AND THE SWITCHGEAR PROVIDING THE ELECTRICAL CIRCUITRY.
 NEC 680.12, FBC 107.2.1
  
 4) INDICATE ON THE PLANS THE LOCATION, WIRING METHOD,
 AND DISCONNECTING MEANS FOR THE CIRCULATION PUMP. NEC
 680.12
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved