| Plan Review Notes For Permit 14040765 |
| Permit Number |
14040765 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-22 12:08:54 | THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL, | | | WITH THE FOLLOWING COMMENT. | | | | | | ON SHEET FA-1 DEVICE 1-4 75CD IS MARKED "E" ON THE LINE | | | DIAGRAM BUT "N" ON THE FLOOR PLAN. THE FIRE INSPECTOR | | | SHALL FIELD VERIFY WITH THE FA CONTRACTOR PROPER CODING | | | AND OPERATION. |
|