| 2014-04-30 16:16:29 | BUILDING/ PLUMBING |
| | PLAN REVIEW |
| | REVISION: 14040755 |
| | PERMIT: 13050713 |
| | ADD: 313 DATURA ST |
| | CONT: ANDERSON MOORE |
| | TEL: (561)662-1819 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 30/ 2014 |
| | ACTION: PROVIO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET A1.01 PLEASE REVIEW ROOF DRAIN RD6 ROOF INLET |
| | INDICATES DRAINING INTO DS5, NOT THE DS6 LABELED 8,814 |
| | SF DISCHARGE. |
| | PLEASE SEE IN THE INLET FOR ROOF DRAIN 6 / 7,276 S FT |
| | OF DRAINAGE? ROOF DRAINS 3 & 4 ALSO DUMP ONTO THIS ROOF |
| | IS THIS FIGURED INTO THE 8,814 SQ FT, IF SO THIS WOULD |
| | BE THE SAME AMOUNT TO BE DRAINED FROM RD6. |
| | PLEASE CONFIRM THE DISCREPANCIES, ALSO SEE ROOF |
| | SCHEDULE A103, ROOF DRAIN # 6 IS NOT PART OF THE |
| | SCHEDULE. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |