| Notes |
| Date |
Text |
| 2014-04-30 18:25:36 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. TWO COMPLETE SETS OF DOCUMENTS REQUIRED FOR PERMIT | | | ISSUANCE, FBC 107. ONLY ONE SET OF THE INSTALLATION | | | SCHEDULE WAS SUBMITTED. FAILURE TO PROVIDE TWO SETS MAY | | | RESULT IN ADMIN/COPY FEES. | | | | | | 2. ONE SET OF THE PRODUCT APPROVALS WAS HIGHLIGHTED, | | | BUT DOES NOT APPEAR TO CORRELATE WITH THIS JOB. FOR | | | INSTANCE, SEE SHEET 12, ACCORDION PRODUCT APPROVAL. THE | | | WOOD ANCHOR SCHEDULE, WOOD SCREWS WAS HIGHLIGHTD, BUT | | | INSTALLATION SCHEDULE INDICATES THAT THIS JOB IS | | | CONCRETE BLOCK. PLEASE PROVIDE PRODUCT APPROVALS WHICH | | | ONLY HAVE MARKINGS WHICH ARE SPECIFIC TO THIS PERMIT. | | | FBC 107. | | | | | | 3. FOR ACCORDION SHUTTERS, ANCHOR SPACING PROPOSED DOES | | | NOT APPEAR TO COMPLY WITH THE REQUIREMENTS OF THE | | | PRODUCT APPROVAL. FOR INSTANCE, SEE OPENING 6. 16" | | | PROPOSED, SEE PAGE 12, 6" REQUIRED FOR A C2 CONNECTION | | | TYPE. THE COLUMN "SHUTTER MOUNTING CONNECTION TYPE" | | | STATES "WALL" BUT SHOULD CORRELATE WITH THE PRODUCT | | | APPROVAL. FOR INSTANCE, FOR THE ACCORDIONS, CONNECTION | | | TYPES ARE C1 THROUGH C5. CHECK ALL AND REVISE | | | ACCORDINGLY. | | | | | | | | | | | | | | | | | | | | | |
|