| 2014-04-23 09:08:26 | PLUMBING / FUEL GAS PLAN REVIEW |
| | PERMIT: 14040739 |
| | ADD: 1409 GEORGIA AVE |
| | CONT: DON LIPSCOMB PLUMBING |
| | TEL: (561)310-9245 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 23/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE ADDITIONAL INFORMATION, THE PLANS |
| | INDICATE TYING INTO A EXISTING 3/4 INCH LINE AT METER. |
| | PLEASE REVIEW THE MINIMUM REQUIREMENTS FOR FUEL GAS |
| | PLAN REVIEW CRITERIA. |
| | GAS PERMIT APPLICATION REQUIREMENTS |
| | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL |
| | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING |
| | IN THE CITY OF WEST PALM BEACH: |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| | FBC-2010 FUEL GAS. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| | PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS |
| | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| | THE SYSTEM. REFER TO THE FBC-2010 FUEL GAS SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(35) |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2010 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) |
| | |
| | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2010 FUEL GAS CODE SEC. 304 |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2010 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. |
| | |
| | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2010 FUEL GAS CODE |
| | SEC. 502 THRU 505. |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2010 FUEL GAS SEC. 402.2 |
| | |
| | 10. 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | R315.1 CARBON MONOXIDE PROTECTION. |
| | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. |
| | EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING |
| | BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR |
| | UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN |
| | SECTION R315.1.3. |
| | R315.1.1 CARBON MONOXIDE ALARM. |
| | THE REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED |
| | BY PROVIDING FOR ONE OF THE FOLLOWING ALARM |
| | INSTALLATIONS: |
| | (1) A HARD-WIRED CARBON MONOXIDE ALARM. |
| | (2) A BATTERY-POWERED CARBON MONOXIDE ALARM. |
| | (3) A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE |
| | ALARM. |
| | (4) A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND |
| | SMOKE ALARM. |
| | |
| | |