| Plan Review Notes For Permit 14040733 |
| Permit Number |
14040733 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-24 08:35:56 | THE FOLLOWING ITEMS SHALL BE ADDRESSED FOR APPROVAL OF | | | THIS PERMIT: | | | 1. INDICATE THE SOURCE OF THE 120 VOLT CIRCUIT ALONG | | | WITH THE METERING AND CONNECTIONS. | | | 2. INCLUDE THE NEC 110.16 FLASH PROTECTION WARNING | | | 3. MAKE CERTAIN THAT ALL SERVICE EQUIPMENT IS WELL | | | CLEAR OF THE ELECTRICAL DATUM PLANE AS PER NEC 682.10 |
|