| Date |
Text |
| 2014-04-29 07:38:13 | PLUMBING PROVISO: |
| | 2010 FBC-EXISTING BUILDING CODE: |
| | |
| | LEVEL 1 |
| | A HIGH/ LOW DRINKING FOUNTAIN IS REQUIRED. |
| | |
| | ACCESSIBILITY 605.1 GENERAL. ACCESSIBILITY SHALL BE IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. |
| | 2010 FL ACCESSIBILITY CODE: |
| | 202.4 ALTERATIONS AFFECTING PRIMARY FUNCTION AREAS. |
| | IN ADDITION TO THE REQUIREMENTS OF 202.3, AN ALTERATION |
| | THAT AFFECTS OR COULD AFFECT THE USABILITY OF OR ACCESS |
| | TO AN AREA CONTAINING A PRIMARY FUNCTION SHALL BE MADE |
| | SO AS TO ENSURE THAT, TO THE MAXIMUM EXTENT FEASIBLE, |
| | THE PATH OF TRAVEL TO THE ALTERED AREA, INCLUDING THE |
| | REST ROOMS, TELEPHONES, AND DRINKING FOUNTAINS SERVING |
| | THE ALTERED AREA, ARE READILY ACCESSIBLE TO AND USABLE |
| | BY INDIVIDUALS WITH DISABILITIES, UNLESS SUCH |
| | ALTERATIONS ARE DISPROPORTIONATE TO THE OVERALL |
| | ALTERATIONS IN TERMS OF COST PURSUANT TO 202.4.1 |
| | 202.4.1 DISPROPORTIONATE COST. UP TO $9600.00 IN |
| | ACCESSIBILITY UPGRADES ARE REQUIRED IF NOT CODE |
| | COMPLIANT ALREADY. THE DRINKING FOUNTAIN WILL NEED TO |
| | COMPLY WITH: |
| | |
| | 211 DRINKING FOUNTAINS |
| | 211.1 GENERAL. WHERE DRINKING FOUNTAINS ARE PROVIDED ON |
| | AN EXTERIOR SITE, ON A FLOOR, OR WITHIN A SECURED AREA |
| | THEY SHALL BE PROVIDED IN ACCORDANCE WITH 211. |
| | EXCEPTION: IN DETENTION OR CORRECTIONAL FACILITIES, |
| | DRINKING FOUNTAINS ONLY SERVING HOLDING OR HOUSING |
| | CELLS NOT REQUIRED TO COMPLY WITH 232 SHALL NOT BE |
| | REQUIRED TO COMPLY WITH 211. |
| | |
| | 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING |
| | FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| | SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH 602.7. |
| | 602.4 SPOUT HEIGHT. SPOUT OUTLETS SHALL BE 36 INCHES |
| | (915 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | 602.7 DRINKING FOUNTAINS FOR STANDING PERSONS. |
| | SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |