| 2014-04-29 08:22:44 | PLUMBING PROVISO; | | | SHOWER LINER TEST REQUIRED. | | | 312.9 SHOWER LINER TEST. | | | WHERE SHOWER FLOORS AND RECEPTORS ARE MADE WATER-TIGHT | | | BY THE APPLICATION OF MATERIALS REQUIRED BY SECTION | | | 417.5.2, THE COMPLETED LINER INSTALLATION SHALL BE | | | TESTED. THE PIPE FROM THE SHOWER DRAIN SHALL BE PLUGGED | | | WATER TIGHT FOR THE TEST. THE FLOOR AND RECEPTOR AREA | | | SHALL BE FILLED WITH POTABLE WATER TO A DEPTH OF NOT | | | LESS THAN 2 INCHES (51 MM) MEASURED AT THE THRESHOLD. | | | WHERE A THRESHOLD OF AT LEAST 2 INCHES (51 MM) HIGH | | | DOES NOT EXIST, A TEMPORARY THRESHOLD SHALL BE | | | CONSTRUCTED TO RETAIN THE TEST WATER IN THE LINED FLOOR | | | OR RECEPTOR AREA TO A LEVEL NOT LESS THAN 2 INCHES (51 | | | MM) DEEP MEASURED AT THE THRESHOLD. THE WATER SHALL BE | | | RETAINED FOR A TEST PERIOD OF NOT LESS THAN 15 MINUTES, | | | AND THERE SHALL NOT BE EVIDENCE OF LEAKAGE. |
|