| Plan Review Notes For Permit 14040680 |
| Permit Number |
14040680 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-29 08:12:41 | BUILDING PROVISO: | | | 1) BEFORE THE INSTALLATION OF FLOOR INSULATION SUBMIT | | | MANUFACTURERS TEST FOR COMPLIANCE WITH: | | | 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING | | | FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF | | | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING | | | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX | | | OF NOT MORE THAN 100. | | | | | | | | | | | | FBC-B 2010 | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|