2014-04-24 14:02:45PERMIT IS READY FOR ISSUANCE WITH THE FOLLOWING
 PROVISO:
 FBC 105.1 REQUIRES A SEPARATE ELECTRICAL PERMIT TO BE
 AQUIRED FOR THE ELECTRICAL WORK INVOLVED TO CONNECT THE
 7.5 HP ELECTRICAL IRRIGATION PUMP TO THE "EXISTING
 SOURCE".
 SECTION 107.2.5 AND 107.3.5 STATE IN PART. "THE
 CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION
 FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN." PLEASE
 INCLUDE LOCATION OF THE "EXISTING SOURCE OF ELCTRICAL
 POWER IN RELATION TO THE LOCATION OF THE NEW 7.5 HP
 PUMP AND INCLUDE DETAILS COVERRING OCPD, GROUNDING, PER
 NEC 250, AND WIRING METHODS AND MATERIALS. PER NEC
 2008.
  