| Plan Review Notes For Permit 14040661 |
| Permit Number |
14040661 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-24 14:02:45 | PERMIT IS READY FOR ISSUANCE WITH THE FOLLOWING | | | PROVISO: | | | FBC 105.1 REQUIRES A SEPARATE ELECTRICAL PERMIT TO BE | | | AQUIRED FOR THE ELECTRICAL WORK INVOLVED TO CONNECT THE | | | 7.5 HP ELECTRICAL IRRIGATION PUMP TO THE "EXISTING | | | SOURCE". | | | SECTION 107.2.5 AND 107.3.5 STATE IN PART. "THE | | | CONSTRUCTION DOCUMENTS SUBMITTED WITH THE APPLICATION | | | FOR PERMIT SHALL BE ACCOMPANIED BY A SITE PLAN." PLEASE | | | INCLUDE LOCATION OF THE "EXISTING SOURCE OF ELCTRICAL | | | POWER IN RELATION TO THE LOCATION OF THE NEW 7.5 HP | | | PUMP AND INCLUDE DETAILS COVERRING OCPD, GROUNDING, PER | | | NEC 250, AND WIRING METHODS AND MATERIALS. PER NEC | | | 2008. | | | | | 2014-04-24 11:50:30 | | | | | | | |
|