| 2014-06-03 14:30:21 | 5335 N. MILITARY TR. #40 AND 65 |
| | |
| | NOTE: ALTHOUGH THE 2ND ELECTRICAL REVIEW CONFLICTS WITH |
| | THE 1ST REVIEW IT SHALL OVERIDE AND DEEM THE 1ST REVIEW |
| | NULL AND VOID. |
| | |
| | 2ND ELECTRICAL REVIEW: |
| | |
| | ACTION: DENIED. |
| | |
| | CODE REFFRENCE: 2008 NEC AND 2010 FBC |
| | |
| | 1) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE |
| | SUPPLIED BY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| | TOGETHER AT THEIR SUPLY END BUT NOT CONNECTED TOGETHER |
| | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| | ONE SERVICE. NEC 230.2 (NUMBER OF SERVICES) |
| | THE RISER AND FLOOR PLAN AS CURRENTLY SHOWN ON SHEET |
| | E-1 INDICATES THIS EXACT CONDITION PROHIBITED BY THE |
| | CODE NOTED ABOVE. PLEASE MAKE CORRECTION TO THIS |
| | CONDITION AND RE-SUBMIT. |
| | |
| | 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI |
| | PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF |
| | THE NEC. |
| | |
| | 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY |
| | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS |
| | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND |
| | CONNECTED AHEAD OF ANY LOCAL SWITCHES. SEE ARTICLE |
| | 701.11(G) OF THE 2008 EDITION OF THE NEC. |
| | |
| | 3) CHILD CARE FACILITIES SHALL COMPLY WITH THE 2010 |
| | EDITION OF THE FBC SECTION 436 SEE SECTION BELOW: |
| | INITIATION OF THE REQUIRED FIRE ALARM SYSTEM SHALL BE |
| | BY MANUAL MEANS AND BY OPERATION OF ANY REQUIRED SMOKE |
| | DETECTORS AND REQUIRED SPRINKLER SYSTEMS. FBC 436.7.1 |
| | |
| | 4) OCCUPANT NOTIFICATION SIGNALS SHALL BE AUDIBLE AND |
| | VISUAL SIGNALS IN ACCORDANCE WITH NFPA 72 AND THE |
| | FBC-ACCESSIBILITY. THE GENERAL EVACUATION ALARM SIGNAL |
| | SHALL OPERATE THROUGHOUT THE ENTIRE BUILDING. FBC |
| | 436.7.1.1 |
| | |
| | 5) A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN |
| | ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN |
| | EACH STORY IN FRONT OF DOORS TO STAIRS AND IN THE |
| | CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAYCARE |
| | OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN |
| | LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY |
| | CARE OCCUPANCY. 436.7.2 |
| | |
| | 6) SEPARATE ELECTRICAL PERMITS ARE REQUIRED FOR LOW |
| | VOLTAGE SCOPE INCLUDING SECURITY ALARM, CCTV, FIRE |
| | ALARM, DATA/COM, AND ACCESS CONTROL, |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. |
| | 561-805-6717 OR [email protected] |
| 2014-05-14 17:58:11 | NEW SHEETS SUBMITTED. JG. |