| Notes |
| Date |
Text |
| 2014-04-22 14:46:16 | THIS PLAN WAS REVIEWED BY PETER LEDUC, FIRE MARSHAL, | | | WITH THE FOLLOWING COMMNETS. | | | | | | ON SHEETS LS-1 AND E-2, PLEASE ADD AN "EM" LIGHT IN | | | REAR HALLWAY WHERE INDICATED AND MOVE THE "EM" LIGHT | | | FROM LEFT SIDE OF HALLWAY TO THE RIGHT SIDE. | | | | | | ON SHEET E-1 AT THE FRONT LOBBY AND RECEPTION AREA IT | | | INDICATES "BUZZER RELEASE". THE EXIT DOORS IN THAT AREA | | | CAN'T BE LOCKED AGAINST EGRESS. PLEASE REFER TO THE | | | DELAYED EGRESS CODE IN CHAPTER 7 OF THE FLORIDA FIRE | | | PREVENTION CODE FOR GUIDENCE. |
|