| Plan Review Notes For Permit 14040657 |
| Permit Number |
14040657 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-05-12 13:15:40 | ELECTRICAL PROVISO: | | | | | | 1) RECEPTACLES FOR WATER COOLERS SHALL BE GFI | | | PROTECTED. SEE ARTICLE 422.52 OF THE 2008 EDITION OF | | | THE NEC. | | | | | | 2) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY | | | AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS | | | THAT SERVING THE NORMAL LIGHTING IN THE AREA AND | | | CONNECTED AHEAD OF ANY LOCAL SWITCHES. SEE ARTICLE | | | 701.11(G) OF THE 2008 EDITION OF THE NEC. | | | | | | 3) CONDUCTORS SHALL BE PERMITTED TO BE TAPPED WITHOUT | | | OVERCURRENT PROTECTION AT THE TAP TO A FEEDER AS | | | SPECIFIED IN 240.21(B)(1) THROUGH B(5) SEE ARTICLE | | | 240.21(B) OF THE 2008 EDITION OF THE NEC. THE RISER | | | DIAGRAM AS SHOWN ON PLANS DOES NOT APPEAR TO BE IN | | | COMPLIANCE. VERIFY EXISTING CONDITION IN THE FIELD. | | | | | | 4) SEPARATE ELECTRICAL PERMITS ARE REQUIRED FOR LOW | | | VOLTAGE SCOPE INCLUDING SECURITY ALARM, CCTV, FIRE | | | ALARM, DATA/COM, AND ACCESS CONTROL, | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] | | | |
|