| 2014-05-03 07:18:40 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) ITEM #3 FROM FIRST REVIEW. THE LOCATION OF THE WATER | | | CLOSET SPECIFIED ON THE PLANS APPEARS TO PREVENT THE | | | REQUIRED ACCESS TO THE A/C EQUIPMENT FOR INSPECTION, | | | SERVICE, REPAIR AND REPLACEMENT. SEE FBCR M1305.1 | | | REMOVING THE WATER CLOSET TO PROVIDE ACCESS TO THE A/C | | | EQUIPMENT IS NOT AN OPTION THAT WOULD COMPLY WITH THE | | | BUILDING CODE REQUIREMENTS. ONE OPTION WOULD BE TO | | | INSTALL AN ACCESS DOOR ON THE OTHER SIDE OF THE CLOSET | | | THAT WOULD OPEN INTO THE HALLWAY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|