| Plan Review Notes For Permit 14040650 |
| Permit Number |
14040650 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-04-22 11:45:41 | NEC | | | TABLE 310.15(B)(6) CONDUCTOR TYPES AND SIZES FOR | | | 120/240-VOLT, 3-WIRE, SINGLE-PHASE DWELLING SERVICES | | | AND FEEDERS. | | | THE PLAN SUBMITTED INDICATES A 1/0? IN 2" C. PLEASE | | | INDICATE THE APPROPRIATE SIZE OF WIRE TO FEED A 200AMP | | | MAIN INCLUDING THE MATERIAL (ALUMINUM OR COPPER) AND | | | THE INSULLATION TYPE. | | | | | | 210.70 LIGHTING OUTLETS REQUIRED. LIGHTING OUTLETS | | | SHALL BE INSTALLED WHERE SPECIFIED IN 210.70(A), (B), | | | AND (C). | | | PLEASE PROVIDE ADDITIONAL LIGHTING OUTLETS PER 210.70 | | | OR INDICATE ON THE PLANS THAT THE PROJECT IS ALREADY IN | | | COMPLIANCE. | | | | | | FBC 107.2.1 "CONSTRUCTION DOCUMENTS SHOULD BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF WORK PROPOSED. " | | | THE PLAN'S RISER SUBMITTED INDICATES A DISC.? JUST TO | | | THE LEFT OF THE METER. PLEASE INDICATE WHAT THIS IS, | | | HOW IT IS FED, AND WHAT IT FEEDS. | | | | | | |
|