Plan Review Notes
Plan Review Notes For Permit 14040647
Permit Number 14040647
Review Stop E
Sequence Number 1
Notes
Date Text
2014-04-22 12:48:00NEC
 (1). 110.3 LISTING ON ALL ELECTRICAL EQUIPMENT AND
 COMPONENTS IS REQUIRED.
 (2) 210.8(B)(4) REQUIRES GFI PROTECTION FOR PERSONNEL
 "OUTDOORS".
 (3) 314.15 IN DAMP OR WET LOCATIONS, BOXES, CONDUIT
 BODIES, AND FITTINGS SHALL BE PLACED OR EQUIPPED SO AS
 TO PREVENT MOISTURE FROM ENTERING OR ACCUMULATING
 WITHIN THE BOX, CONDUIT BODY, OR FITTING. BOXES,
 CONDUIT BODIES, AND FITTINGS INSTALLED IN WET LOCATIONS
 SHALL BE LISTED FOR USE IN WET LOCATIONS.
 (4) 300.6 PROTECTION AGAINST CORROSION AND
 DETERIORATION. RACEWAYS, CABLE TRAYS, CABLEBUS,
 AUXILIARY GUTTERS, CABLE ARMOR, BOXES, CABLE SHEATHING,
 CABINETS, ELBOWS, COUPLINGS, FITTINGS, SUPPORTS, AND
 SUPPORT HARDWARE SHALL BE OF MATERIALS SUITABLE FOR THE
 ENVIRONMENT IN WHICH THEY ARE TO BE INSTALLED. IF THERE
 IS A POTENTIAL FOR SPILLAGE OF CORROSIVE MATERIALS FROM
 VEHICLES, PLEASE COMPLY WITH 300.6.
  
 FBC
 107.2.1 "CONSTRUCTION DOCUMENTS SHOULD BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION NATURE AND EXTENT OF
 THE WORK PROPOSED."
 NO ELEVATION IS INDICATED FOR RECEPTACLE OUTLET. PLEASE
 PROVIDE AN ELEVATION AND SHOW METHOD(S) FOR DRAINAGE
 FROM THE PIT FOR ACCUMULATION OF RAIN WATER, CORROSIVE
 WASTE MATERIALS AND WASHDOWN WATER.