| 2014-04-29 05:31:08 | PLUMBING PLAN REVIEW | | | PERMIT: 14040618 | | | ADD: 3111 45TH ST SUITE # 15B | | | CONT: LTL BUILDERS | | | TEL: (561)478-1845 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. APRIL 28/ 2014 | | | ACTION:DENIED | | | | | | 1) THE TENANT SPACE IS MISSING A SERVICE SINK REQUIRED | | | FOR ASSEMBLY TYPE OCCUPANCY 2010 FBC-P TABLE 403.1. | | | | | | 2) PLEASE PROVIDE A WASTE ISOMETRIC INDICATING THE | | | CONTINUATION OF THE BRANCH WASTE LINE TO THE BUILDING | | | DRAIN, PLEASE INDICATE WHERE THE TENANT 15A'S GREASE | | | INTERCEPTOR WOULD BE AND A TIE INTO THE BUILDING DRAIN | | | AFTER THE GREASE INTERCEPTOR. THE GREASE INTERCEPTOR | | | WOULD NOT HAVE BEEN SIZED FOR THE ADDITIONAL FLOW NOR | | | SHOULD THE RESTROOM WASTE. 2010 FBC-P 1003.3.1. | | | | | | 3) PROVISO: THE FINISH RESTROOM MEASUREMENT NEEDS TO BE | | | 7'-1", NOT ROUGH. 2010 FBC- ACCESSIBILITY 604.3.2 AND | | | FIGURE 604.8.1.6.) | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|