| Date |
Text |
| 2014-04-28 18:59:45 | BUILDING PLAN REVIEW |
| | PERMIT: 14040618 |
| | ADD: 3111 45TH ST SUITE # 15B |
| | CONT: LTL BUILDERS |
| | TEL: (561)478-1845 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. APRIL 28/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) ) PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION (TYPE |
| | OF BUSINESS) BETWEEN TENANT 15B. THE COVER SHEET |
| | INDICATES THE SAME A2 |
| | OCCUPANCY. THIS CLASSIFICATION INCLUDES BANQUET HALLS, |
| | NIGHTCLUBS AND RESTAURANTS, THE LEFT HAND TENANT SPACE |
| | DOES NOT HAVE A LIFE SAFETY PLAN SHOWING THE LAYOUT OF |
| | FURNITURE, AND EGRESS PATH FOR THIS TYPE OF OCCUPANCY. |
| | 2010 FBC-B 303.1 & 107.3.5.1.1MINIMUM CRITERIA FOR |
| | COMMERCIAL PLAN REVIEW. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| | (7) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | |
| | 2) THE COVERSHEET INDICATES NEW TENANT SEPERATION WALL, |
| | PLEASE PROVIDE CODE COMPLIANCE FORTHE NEW AND EXISTING |
| | KITCHEN WALL; |
| | 2010 FBC-B 709.1(6) TENANT SEPERATION WALLS 1 HR. |
| | PLEASE NOTE THERE MAY BE A OCCUPANCY CHANGE, IT MAY END |
| | UP A 2 HR FIRE RATED WALL. |
| | 709.2 MATERIALS. |
| | THE WALLS SHALL BE OF MATERIALS PERMITTED BY THE |
| | BUILDING TYPE OF CONSTRUCTION. |
| | |
| | 709.3 FIRE-RESISTANCE RATING. |
| | FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF |
| | NOT LESS THAN 1 HOUR. |
| | |
| | 709.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE |
| | TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW |
| | TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB |
| | OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| | BE SECURELY ATTACHED THERETO. IF THE PARTITIONS ARE NOT |
| | CONTINUOUS TO THE SHEATHING, DECK OR SLAB, AND WHERE |
| | CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION, THE SPACE |
| | BETWEEN THE CEILING AND THE SHEATHING, DECK OR SLAB |
| | ABOVE SHALL BE FIREBLOCKED OR DRAFTSTOPPED IN |
| | ACCORDANCE WITH SECTIONS 717.2 AND 717.3 AT THE |
| | PARTITION LINE. |
| | |
| | 3) SHEET D1.0 & A1.0 BOTH INDICATE A NEW EXTERIOR DOOR |
| | WAY BEING CUT INTO THE SOUTHWEST WALL, PLEASE PROVIDE |
| | STRUCTURAL DETAILS FOR COLUMNS, HEADER/ LINTEL FOR THE |
| | NEW OPENING AND THE CONTINUATION OF THE MAIN WIND FORCE |
| | RESISTING SYSTEM (MWFRS). |
| | |
| | 4) PLEASE PROVIDE WIND DESIGN CRITERIA FOR THE NEW |
| | OPENING: 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| | DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: (31)(A) |
| | EXTERIOR DOORS. |
| | |
| | 7) A1.0 DOORS 001WILL NEED TO BE FIRE RATED SINCE THEY |
| | DO CREATE A COORIDOR IN A NON-SPRINKLERED BUILDING. |
| | TABLE 715.4. ALSO SEE VESTIBULES |
| | 1027.1 EXCEPTION # 2. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2014-04-17 11:35:36 | IN B18 |