Plan Review Notes
Plan Review Notes For Permit 14040617
Permit Number 14040617
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-20 18:08:57BUILDING PLAN REVIEW
 PERMIT:14040617 POOL FENCE
 ADD: 300 COURTNEY LAKES
 CONT: KAST CONSTRUCTION
 TEL: (954)587-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY MAY 20/2014
 ACTION: DENIED
  
 1) INCLUDED UNDER THIS PERMIT ARE ARCHITECTURAL,
 PLUMBING & ELECTRICAL SHEETS THAT WERRE REVIEWED UNDER
 THE CLUBHOUSE PERMIT (13051012) ADDRESS 290 COURTNEY
 LAKES, THEY SHOW AS REVISION # 2 UNDER THE
 ARCHITECTURAL, AND REVISION # 1 UNDER THE ELECTRICAL &
 PLUMBING SHEETS. TO BE REVIEWED UNDER A REVISION TO THE
 CLUBHOUSE PERMIT. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2010 EDITION 107.3.4.2 DEFERRED SUBMITTALS,
 (REVISIONS).
  
 2) CIVIL AND HARDSCAPE PLANS WERE ALSO SUBMITTED WHICH
 ARE NOT PART OF THE FENCE PACKAGE, PLEASE REMOVE THESE
 PLANS AND SUBMIT UNDER THE APPROPRIATE PERMIT OR
 REVISION. NOTE THE POOL DECK WILL NEED TO SUBMIT
 SEPERATE PLANS FOR REVIEW AT THIS TIME IT CAN NOT BE
 DETERMINED WHAT PLANS ARE TO BE REVIEWED UNDER WHICH
 PERMIT, THERE ARE CIVIL PLANS SUBMITTED SHOWING THE
 UNDERGROUND FIRE LINES? 2010 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
 3) THIS PERMIT HAS NOT HAD THE PLAN REVIEW FEES PAID,
 BEFORE THE NEXT REVIEW CYCLE THESE FEES MUST BE PAID OR
 NO REVIEW WILL BE STARTED. 108.3* BUILDING PERMIT
 VALUATION
  
 4) PLEASE SHOW COMPLIANCE WITH THE 2010 FBC-B
 424.1.3.1.9
 ALL PUBLIC POOLS SHALL BE SURROUNDED BY A MINIMUM 48
 INCH (1219 MM) HIGH FENCE OR OTHER APPROVED SUBSTANTIAL
 BARRIER. THE FENCE SHALL BE CONTINUOUS AROUND THE
 PERIMETER OF THE POOL AREA THAT IS NOT OTHERWISE
 BLOCKED OR OBSTRUCTED BY ADJACENT BUILDINGS OR
 STRUCTURES AND SHALL ADJOIN WITH ITSELF OR ABUT TO THE
 ADJACENT MEMBERS. ACCESS THROUGH THE BARRIER OR FENCE
 FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS, MOTEL
 ROOMS AND HOTEL ROOMS, SHALL BE THROUGH SELF-CLOSING,
 SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM)
 MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH THE LATCH
 LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM THE
 BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM) BELOW
 THE TOP OF THE GATE ON THE POOL SIDE. IF THE
 SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING
 AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR
 INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF
 SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864
 MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED
 FLOOR OR GROUND. GATES SHALL OPEN OUTWARD AWAY FROM THE
 POOL AREA. A LATCHED, LOCKABLE GATE SHALL BE PLACED IN
 THE FENCE WITHIN TEN FEET (3048 MM) OF THE CLOSEST
 POINT BETWEEN THE POOL AND THE EQUIPMENT AREA FOR
 SERVICE ACCESS.
  
 INSTEAD OF A FENCE, PERMANENT NATURAL OR MAN-MADE
 FEATURES SUCH AS BULKHEADS, CANALS, LAKES, NAVIGABLE
 WATERWAYS, ETC., ADJACENT TO A POOL MAY BE PERMITTED AS
 A BARRIER WHEN APPROVED. WHEN EVALUATING SUCH BARRIER
 FEATURES, THE APPLICABLE GOVERNING BODY MAY PERFORM
 ONSITE INSPECTIONS, AND REVIEW EVIDENCE, SUCH AS
 SURVEYS, AERIAL PHOTOGRAPHS, WATER MANAGEMENT AGENCY
 STANDARDS AND SPECIFICATIONS, AND ANY OTHER SIMILAR
 DOCUMENTATION TO VERIFY AT MINIMUM, THE FOLLOWING: THE
 BARRIER FEATURE IS NOT SUBJECT TO NATURAL CHANGES,
 DEVIATIONS OR ALTERATIONS AND IS CAPABLE OF PROVIDING
 AN EQUIVALENT LEVEL OF PROTECTION AS THAT PROVIDED BY A
 STRUCTURE, AND THE BARRIER FEATURE CLEARLY IMPEDES,
 PROHIBITS OR RESTRICTS ACCESS TO THE POOL.
  
 5) UNDER THE FAIR HOUSING ACT DESIGN MANUAL, CHART 2.4
 DIAGRAM 2.8 A SWIMMING POOL MUST BE LOCATED ON AN
 ACCESSIBLE ROUTE,GATE ACCESSING THE POOL MUST MEET
 REQUIREMENT 3 AND THE ROUTE MUST PROVIDE ACCESS TO THE
 DECK AROUND THE POOL. SHOW COMPLIANCE.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676