| 2014-04-29 17:37:26 | BUILDING PLAN REVIEW |
| | PERMIT: 14040616 |
| | ADD: 4375 EASLEY ST |
| | CONT: TBD |
| | TEL: (561)835-7429 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 29/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 3) SHEET A4.1 DIVISION 9 FINISHES. INDICATES THE USE OF |
| | ACOUSTICAL CEILING SYSTEMS PLEASE PROVIDE COMPLIANCE |
| | WITH: |
| | 808.1 ACOUSTICAL CEILING SYSTEMS. |
| | THE QUALITY, DESIGN, FABRICATION AND ERECTION OF METAL |
| | SUSPENSION SYSTEMS FOR ACOUSTICAL TILE AND LAY-IN PANEL |
| | CEILINGS IN BUILDINGS OR STRUCTURES SHALL CONFORM WITH |
| | GENERALLY ACCEPTED ENGINEERING PRACTICE, THE PROVISIONS |
| | OF THIS CHAPTER AND OTHER APPLICABLE REQUIREMENTS OF |
| | THIS CODE. |
| | 808.1.1 MATERIALS AND INSTALLATION. |
| | ACOUSTICAL MATERIALS COMPLYING WITH THE INTERIOR FINISH |
| | REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S RECOMMENDATIONS AND |
| | APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH. |
| | 808.1.1.1 SUSPENDED ACOUSTICAL CEILINGS. |
| | SUSPENDED ACOUSTICAL CEILING SYSTEMS SHALL BE INSTALLED |
| | IN ACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND |
| | ASTM C 636. |
| | |
| | 4) SHEET A4.1 DIVISION 9 FINISHES. PLEASE SEE USE OF |
| | DRYWALL IN WET AREAS, 2509.1 WET AREAS. |
| | SHOWERS AND PUBLIC TOILET WALLS SHALL CONFORM TO |
| | SECTIONS 1210.2 AND 1210.3. |
| | |
| | 2509.2 BASE FOR TILE. |
| | GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| | DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| | SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| | SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| | OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | 2509.3 LIMITATIONS. WATER-RESISTANT GYPSUM BACKING |
| | BOARD SHALL NOT BE USED IN THE FOLLOWING LOCATIONS: |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING |
| | BOARD AND MORE THAN 16 INCHES (406 MM) O.C. FOR |
| | 5/8-INCH-THICK (15.9 MM) WATER-RESISTANT GYPSUM BACKING |
| | BOARD. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |